Outdoor CO2 transmitter
ID:eSenseOutdoor
The eSENSE Outdoor PCB is housed in an IP65 housing with breathers to support the flow of outdoor air. The eSENSE Outdoor includes an in-line thermostat in order that heating of the housing only takes place when the outdoor temperature warrants the use of the energy to maintain an above freezing temperature in the housing. Maintaining an above freezing temperature prevents the accumulation of ice crystals inside the Optical Bench Assembly, which could cause inaccurate CO2 measurements.
-
- Compliance with ............................................... EMC directive 89/336/EEC. RoHS directive 2002/95/EG
- Operating Temperature Range ........................ -22 to +115 °F
- Operating Humidity Range ............................... 0 to 95% RH (non-condensing)
- Operating Environment .....................................Outdoor
- Warm-up Time .................................................. < 1 min. (@ full specs < 15 minutes)
- Sensor Life Expectancy .................................... > 15 years
- Maintenance Interval ........................................ no maintenance required
- Self Diagnostics ................................................ complete function-check
- Power Input ...................................................... 24 VAC/VDC ±20%, 50 Hz (half-wave rectifier input)
- Power Consumption ......................................... < 1 Watt average (Heater Off)
- Output signal terminal CO2
- OUT1 linear conversion range........................... 0 - 10 VDC for 0 - 2 000 ppm.
- OUT2 linear conversion range ........................... 4 - 20 mA or 2 – 10VDC for 0 - 2 000 ppm.